Experimental Measurements of Condensation Heat Transfer Coefficients for Refrigerant HFO-1234yf 2013-01-1493

Experimental tests were conducted on a parallel flow condenser with HFO-1234yf as the working fluid on an AC system bench to determine average and local heat transfer coefficients during condensation of HFO-1234yf for mass flow rates that are typically encountered from idle to highway speeds (800 to 3000 rpms). A condenser from MY 2008 medium-sized sedan was used for this investigation. All original OEM parts were used with the alternate refrigerant. Same TXV set-point was used with HFO-1234yf. The magnitude of the measured heat transfer coefficient for condensation was found to be 8~12% lower in comparison to HFC-134a. The magnitudes of the pressure drop during condensation were of the same magnitude as HFC-134a system. The information from this investigation can be used to in the design of condensers for mobile air conditioning systems with HFO-1234yf as the working fluid.