1984-10-01

Fast Start System for a 200-KW Gas Turbine Generator Set 841568

Emergency standby generator systems require rapid start characteristics capable of providing on-line operation within 10 seconds under a wide range of environmental conditions. This paper describes the design and development of a fast start, air impingement system for a 200-kW, single-shaft, gas turbine generator set. The conventional electric start system was replaced by a high pressure, air start system which reduced the total start-to-load time from 21 to 9 seconds.

SAE MOBILUS

Subscribers can view annotate, and download all of SAE's content. Learn More »

Access SAE MOBILUS »

Members save up to 43% off list price.
Login to see discount.
Special Offer: Purchase more aerospace standards and aerospace material specifications and save! AeroPaks off a customized subscription plan that lets you pay for just the documents that you need, when you need them.
X