Steady State Characterization of Arcing in 540 V dc Distribution Systems

2017-09-19
2017-01-2035
As applications in aerospace, transportation and data centers are faced with increased electric power consumption, their dc operating voltages have increased to reduce cable weight and to improve efficiency. Electric arcs in these systems still cause dangerous fault conditions and have garnered more attention in recent years. Arcs can be classified as either low impedance or high impedance arcs and both can cause insulation damage and fires. Low impedance arcs release lots of energy when high voltage becomes nearly shorted to ground. High impedance arcs can occur when two current-carrying electrodes are separated, either by vibration of a loose connection or by cables snapping. The high impedance arc decreases load current due to a higher equivalent load impedance seen by the source. This complicates the differentiation of a high impedance arc fault from normal operation.